Friday, 25 May 2012
Tuesday, 22 May 2012
Monday, 21 May 2012
Real And Reactive Power
KVA,KW,KVAR,KWh,Kvar.....
As an electrical engineer we seen a lot as KW,MW,KVA etc.
These are some units related with power and energy. It varies with the nature
of the power and energy. Before that we can just see what is reactive and real
power.
REACTIVE POWER:
The book
definition is ‘it is the power absorbed by the inductor or released by the
capacitor’. We know in AC circuit only the inductance and capacitance are
present. It may be a line capacitance or winding inductance.It is the imaginary
power etc.
This reactive power is simply
circulating power due to the phase shift between the source and the loads. This
additional power that appears to be flowing requires the equipment to be rated
higher than that for a system operating at unity. Obviously these circulating
currents while real..produce no useful work. It is the job of the Electrical Engineer
to correct the load reactance as close as possible to unity to increase
efficiency and reduce operational costs. That means simply match the
capacitance and inductance.
Start now,
Total power KVA = Kilo Volt Amp(v*I)
Total power KVA = Kilo Volt Amp(v*I)
Real
power KW =
Kilo Watt(v*I*cosΦ)
Reactive power KVAR = Kilo Volt Amp Reactance (v*I*sinΦ)
Reactive power KVAR = Kilo Volt Amp Reactance (v*I*sinΦ)
Total power KVA=KW+jKVAR
Power * Time= Energy
Eg:KW*Hour=KWh(unit of electrical energy)
Friends, the field of reactive power is a wide area and researches
are now going on, so i am not yet expert. The interesing fact is Reactive power
is needed to transport the real power!! So we minimize it what ever we can. We use
capacitor banks and other FACTS(Flexible AC Transmission System) devices for
minimize it.
Sunday, 20 May 2012
Star and Delta Connections
STAR AND DELTA CONNECTIONS
We seen the 3 phase concept and now we can discuss the star
and delta connection for 3 phase supply. Actually where is these connections
exist? The answer is at
· Transformers(Both power and instrumentation).
· At motor winding.
· At generator winding.
Actually where we handle the 3 phase supply directly, we can
prefer the star or delta connection. Previous post i mentioned that only 3
phase loads are motors,so you may confuse about the transformers, actually
transformer is not a load. It just change the voltage level.
Delta connection is also used to connect the windings of
most three-phase motors because the phase windings are perfectly balanced and,
therefore, do not require a neutral connection.
Making a star connection has the advantage
that two voltages
become
available – a line voltage between any two phases, and a
phase
voltage between line and neutral which is connected to the star point.
In any star-connected system currents
fl ow along the lines ( IL), through
the load and return by the neutral conductor connected to the star point. In a balanced three-phase system all currents have the same
value and when they are added up by phasor addition, we find the resultant
current is zero.
3 Phase Concept
WHY WE USE 3 PHASE ?
In the electrical field we use only 3
phases exactly. Not more or less,Why? Because we minimum of 3 phases to produce
a rotating magnetic field(RMF). We studied that more than one phase is enough
to produce a torque, but imagine 2 equal magnitude phases come into action the
phase angle will be 1800 and
will oppose each other.
So we use 3 phases to produce a
rotating magnetic field and can carry more power than a single phase. Remember one
thing, the only 3 phase AC loads are motors. No other loads are directly
consume or use the 3 phase AC supply. You can easily understand the concept with
an IC engine with 3 cylinder.
Friday, 18 May 2012
Structure Of Power System
STRUCTURE OF POWER SYSTEM
So we discussed about the need for High Voltage,Now we can
see the structure of power system according to the voltage level and the
position of transformers.
From the
structure we clear that at generation and distribution, the voltage is
comparatively less. At the transmission we have very High Voltage. You can
imagine the need for it. At transmission we have long line and loss will high
so we use high voltage at this side simple.......!!
The voltage levels i mentioned above are just a common levels,
It may be vary according to the design.I personally found that the small head
hydro plants have a generating voltage
of 3.3Kv.at this case the sending end transformer has the voltage ratio of
3.3Kv/11Kv .
Thank You For Reading Keep Follow me.........
Thursday, 10 May 2012
Need for High Voltage
Why we are
using High Voltage AC supply..?
Most our
consumer gadgets are using DC supply like TV,Computer,Laptop etc.,then why we
are using AC ?
Because the AC supply voltage only we can
efficiently and easily stepup or stepdown. We can also stepup or stepdown the
DC with the help of modern power electronics devices,but it is complicate and
not much efficient.You all know the transformer is the most efficient machine
in electrical(more than 90%).
Again the question is why stepup or
stepdown the voltage? We can find the answer from the following formula.
We know power P=V*I
Replace ‘V’ with ‘IR’(ohm’s
law)
Power P=I2R
This power
equation shows where ever a resistance present it will consume some power as I2R and
it proportional to the square of the current.
We know our current carrying conductor
has some resistance and they will sure consume the electric power. We don’t
need the conductor to consume the power actually it just waste the power.Our
requirement is to use the power only by the equipment. To avoid this problem we
need to reduce the current!
Only way to minimize the current
without changing the power requirement is to stepup the voltage of the supply
through a transformer.
The following practical example will
clear the whole concept.
Imagine you
have a small factory 50KM away from an electric substation and you need 1000KVA of total power.
Case 1:
You are going to take that without stepup
the voltage, so V=230V
Power P=VI We
know P=1000KVA,V=230V
Current I=1000KVA/230V=4347.82A
Case 2:
You are
going stepup the voltage and transmit,so
V=11KV
Power P=VI We
know P=1000KVA,V=11KV
Current I=1000KVA/11KV=90.909A
From the
case 1 and 2 we can see that higher the voltage lower the current. Advantages
are
1. Less current so less the losses.
2. Need Small Conductor because less
current.
Only
Disadvantage is we need two transformer
and suitable insulation.But it is negligible when we account this for a long
time of operation.
Wednesday, 9 May 2012
Simple Basic
Let’s Start
from the Basics
We heard a lot about the
Current,Voltage,Resistence,Inductance etc...So i am not going to explain it again....just visualize it with
a simple picture.My personal advice to learn electricity by visualize
everything..Because electricity we can’t see,touch!!.....Here i am illustrate
by a water tank...
From the
picture we can understand that to carry more current we need big conductors
...Also we need sufficient Voltage(head of water in the picture).
Convert
Water= Electrons
Water Tank = source of electricity
Pipe= Electric conductor
Convert
Water= Electrons
Water Tank = source of electricity
Pipe= Electric conductor
Through the way,the water may experience some difficulties
cause by friction,Like wise in electrical the current also experience some
opposition caused by RESISTANCE
‘ .
My First Post
Hai All this blog aim for all electrical field friends.Here i am going to share my electrical field experiences that i was got from various working sites.For a fresh electrical engineer or what ever may be...it is hard to know the practical thing apart from your theories.So use this blog to study your ABC in electrical....Keep touch with me.
Subscribe to:
Posts (Atom)